The DAIKIN SKY AIR FTXC50A-AV 5.0kW Reverse Cycle Split System Air Conditioner offers compact and sophisticated design, providing both comfort and flexibility in installation. With interlock control and DIII-NET communication, it's easy to control and maintain. Plus, easy cleaning makes it a breeze to keep your space cool and comfortable.

Get a Quote View full details
Product Specification
 Model Name Indoor unit FTXC50AV1A
Outdoor unit RXC50AV1A
Power supply 1 Phase, 220-240V, 50Hz
Cooling capacity1,3 Rated (Min. – Max.)  kW 5.0(1.4-6.0)
Heating capacity2,3 Rated (Min. – Max.)  kW 6.0(1.4-7.1)
Power consumption Cooling1 kW 1.45
Heating2 kW 1.61
EER Cooling kW/kW 3.45
COP Heating kW/kW 3.73
AEER Cooling 3.33
ACOP Heating 3.61
TCSPF (Cooling) Commercial / Residential Hot 5.31 / 4.81
Average 5.24 / 4.02
Cold 5.55 / 4.03
HSPF (Heating) Commercial / Residential Hot 5.39 / 5.36
Average 4.96 / 4.64
Cold 4.50 / 4.14
Indoor unit Colour Fresh white
Airflow rate (H / M / L) /s 300 / 267 / 233
m3/min 18.0 / 16.0 / 14.0
Sound pressure level4 (H / M / L) dB(A) 45.0 / 42.0 / 40.0
Sound power level (H / M / L) dB(A) 61 / 58 / 56
Dimensions (HXWXD) mm 290X1,050X238
Machine weight kg 13
Certified operation range Cooling °CWB 14 to 25
Heating °CDB 15 to 27
Outdoor Colour Ivory White
unit Compressor Type Hermetically sealed swing type
Motor output kW 1.3
Refrigerant charge (R-32)  kg 1.35(Charged for 30 m)
Sound pressure level 4 Cooling / Heating dB(A) 48 / 51
Night quiet mode dB(A) 44
Sound power level dB(A) 68
Dimensions (HXWXD) mm 595X845X300
Machine weight kg 45
Certified operation range Cooling °CDB -5 to 50
Heating °CWB -15 to 15.5
Piping connections Liquid (Flare) mm o/ 6.4
Gas (Flare) mm o/ 12.7
Drain Indoor unit mm VP13 (I.D.o/ 13XO.D. o/ 18)
Outdoor unit mm o/ 26.0 (Hole)
Max. interunit piping length m 50 (Equivalent length 70)
Max. installation height difference m 30
Heat insulation Both liquid and gas piping